-
-
Attic Venting In Your Home Or
Business
This page has information about buildings with an
attic.
If you don't have an attic it will
still relate to you how important venting of heat really is.
The importance of venting your attic cannot
be overlooked. In hot climates increase your energy costs for air conditioning and make
your house uncomfortable.
Let's start with an understanding of
basic physics: Hot air rises.
But why? Heated air rises due to a differential in density (mass),
which causes an upward movement of the fluid (air is a fluid). Like a lava
lamp, the colored liquid is heated, rises to the top, cools off (density is
increased), then falls back to the bottom.
Think of the force required to
raise a hot air balloon off the ground with 10 passengers, the tanks of propane,
the weight of the basket and the balloon. Pretty impressive force if
you think about it. Should be easy for hot air to rise out of your
attic right? Driven by the density differential, the exhausting of the hot
air should bring in fresh air where vents are located around the base of the
roof (soffit).
There is no "pressure" that drives hot air out of an
attic. The pressure (atmospheric), inside your attic is the same as it is
outside (based on a no wind condition. Wind blown across a roof can create
a positive pressure on the windward side and a lower pressure on the lee
side).
Using a tracer gas and smoke generators, we have
documented all types of attic venting, the appropriate sizes that work in hot
climates and have posted our findings below. This is not a
scientific study but observations made over the study of hundreds of homes in all types of climates.
Our Field Proven Results and
Recommendations: (if using a radiant barrier)
- 10 square feet of venting per 1000 square feet of
attic area minimum. 50% at the peak, 50% at the soffits (with no
radiant barrier, use 8 square feet per 1000 square feet of attic area in hot
sunny climates)
-
Ridge venting, placed at the peak of the
roof while attractive and easy to install when replacing a roofing system, defy gravity,
physics and logic. Hot air rises, this is a law of thermodynamics
yet a ridge vent consists of an inverted "V". This creates a thermal check
valve which does not allow the hot air to escape properly.
- Stay away from solar
attic fans. The claims of CFM movement are overrated. Our testing
has shown a solar fan with an 11 watt panel, (facing South), moves
315CFM. That's less than half of what is advertised. Good idea but
not enough power to spin the fan blade.
- Whirlybirds (the aluminum spinning vents) have less than
one square foot of roof opening and do not induce air movement while
spinning. Larger, less conspicuous static vents are more efficient at
moving air.
- Aspirate your attic
naturally (no power fans) wherever and whenever possible. A well
ventilated attic does not need power venting.
- If you have to use a power fan (tile roofs, inaccessible
areas, flat roofs), don't look for one at a home store, they are not what they
used to be. The older fans (ten years ago), had better motors, better
bearings and a thermostat that could be relied upon to control the
fan. Having installed hundreds in our radiant barrier applications
and replacing most of them (within a year), we were forced to find an
alternative to this liability. Our radiant barrier installations rely
heavily on the removal of the waste heat generated by our products which has
made us venting experts over the last 20 years. We have found a fan made in
Germany used as a poultry house exhauster that is awesome: quiet,
vibration free, has permanently lubricated bearings (never needs oiling),
which we mate with a quality high voltage adjustable thermostat. (scroll
down for more info). If you have to use a fan, this is the one to use.
What works, what doesn't:
CONTINUOUS SOFFIT
VENTING
Continuous soffit venting is typically a 2" or 3" slot cut into the
soffit into which is placed a manufactured venting system made from plastic or
metal. The plastic is typically molded with thousands of small holes
(1/32" in diameter), to keep bugs out. Great idea, easy to install but
falls short of offering suffient net free area to allow air to move.
Another popular type is an aluminum strip with small louvers pressed
into them.
BENEFITS: Easy to install and
attractive.
PROBLEMS: The holes are too small (see photo below), to
pass sufficient air to let the attic aspirate naturally. Most often these
are covered with insulation or partially plugged with dust/pollen/spider webs
over time.
See our formula belo
w for how many to add per square
foot of attic area.

This vinyl soffit covering is very
popular as it completely eliminates the need for painting and/or maintenance on
your home. Great idea! Unfortunately, it starves the attic for air
and costs you money and comfort.
WHIRLYBIRDS
The correct term is "air motor" , also called roof
turbines. It is thought that the spinning turbine creates some sort of
suction which induces air movement. This has not been proven.
These are called "air motors" as they are used in large commercial applications
for venting of smoke and fumes from a manufacturing plant. The wind spins
the turbine which is connected by a shaft to a fan blade below which spins and
pulls the air from the building. Turbines used in the residential market do not
have these fans and therefore can exhaust only what the roof opening
dictates. Pi times the radius squared equals the area. A 10"
unit offers 78.5" of free net area, a 12" 113" square inches.
Venting an attic using natural aspiration is based on free net area.
Use this to calculate the sizes of intake vents (soffit) and exhaust vents (at
the top of the roof).
Despite the small area of
these vents, the vertical stack of this vent allows for the fastest flow of air
from a hot attic. For best performance, these vents should be placed as
close to the peak of the roof as possible.
RIDGE VENTING
This
popular method of attic venting is catching on all over the country.
Easy to install, looks good, inexpensive, doesn't leak...only one problem:
They don't work. Ridge vents defy gravity, physics and basic
thermodynamic principles as outlined below:
- Gravity: Hot air
rises. Hot air will not turn around at the peak and go down hill,
defying gravity.
- Physics: Hot
attic air is less dense than the outside ambient air and defies logic to be
able to exit
Since our reflective attic
insulation products increase attic temperature by the rejection of infrared
heat, attic venting has played an important aspect of looking at the big
picture. Getting rid of this heat is very important to reduce energy
consumption and increase interior comfort. We have found through
experience that homes with ridge venting are historically the hottest and emails
from our customers who have read this site reinforce this over and
over.
Puffing tracer gas inside the attic at 2pm just under the opening shows
the air in the attic to be stagnant. Stay away from ridge venting
unless your home is built where there is a constant breeze as the air moving
over the roof will tend to create a vacuum on the lee side of the roof which
will draw the hot air out.
VENTING IMAGES

If you see these balls
of sap boiled out of your rafters your attic is an oven due to inadequate
venting. This makes your home hot, dries out your structural framing members and
is an indication your may be spending too much to maintain interior
comfort.

Dormer vent being
installed.
A 20" x 20" opening (400 sq. inches or 2.77sq ft) is
made for this 21" x 24" dormer
or "eyebrow" vent .
Actual net free venting area is 97 square
inches.
Ridge
Venting vs. Dormer Vents
Having installed our reflective
radiant
barrier in homes for over 18 years we have found that
the rejected heat, previously absorbed by the insulation (and passed on later),
winds up in the attic making the attic hotter. Much hotter in fact than an
attic without a radiant barrier. This means the attic venting must
be properly sized or install a quality attic fan (seen below), to exhaust the
excess heat. A properly vented attic, be it vented by natural aspiration
(adequate soffit vents and properly sized and placed exhaust vents), or a
powered attic fan, should be only a few degrees above outside ambient
temperature.
Ridge vents are very attractive, easy to install and makes
all the sense in the world...they just don't work. Everyone will agree hot
air rises. Where best to put an attic exhaust vent? At the peak
where the attic air is the hottest?
Sounds logical except for one
basic fact: Hot air rises, it doesn't go down. A ridge vent design dictates hot
air must fight gravity, travel down from
the peak of the roof in order to escape. This of course is unrealistic and
so is expecting this type of vent to be effective. The only "driving
force" that makes hot air leave an attic is the differential density of the 140F
attic compared to the more dense ambient outside air. If you have
any doubts (as we did), as to the function of this type of vent, do what we
did: Buy a 2000 CF smoke canister, place it in a coffee can in the center
of the attic and light it. Then go outside and wait for the smoke to come
out of the ridge vent. Better bring a lunch, plenty of water and a
good book....you will be there awhile.
The
roof you see above was built using a continuous ridge vent. When the hot
weather came in April to this Phoenix home, the attic was like an oven despite
the fact the intake venting (soffits), were doubled to insure good flow.
We cut
the first hole in this roof about noon to install the dormer vents
you see above and the air came out so fast if you kicked the sawdust
into the hole it would hit you in the face! Proof that
the hot, stagnant attic air is not being vented properly and being trapped
by the ridge vent design. Further, the steeper the roof pitch, (like homes
in Texas or the older Cape Cod homes in the Midwest), the less
the ridge vent will work. This observation is based on fact, physics and
common sense. Hot air does not fight gravity.

Dormer vents installed on a home
in Dallas where the hottest attic air temperature was ever recorded by our NRG
Auditor. Two reasons:
1) The underside of the roof decking was sprayed
with silver radiant barrier paint thus lowering the emissivity and increasing the
convective currents (and energy use), in the attic
space.
2) Ridge vents trapped the hot air. Ridge vents rely on some
unknown source of the universe to drive hot air down then out. The dormers
shown here dropped the attic temp by 42 degrees. Solution: TCM6 over the insulation and Dormers.
SOFFIT VENTING
Many homes do
have soffit vents but are blocked by improperly installed insulation.
Proper attic ventilation is necessary and the products listed below will help.
This is what you may see when you
look at your venting around the perimeter of your
home
"My attic has
hundreds of holes around the perimeter, we don't need any more
venting"
Remove the blocking
and you can see the fiberglass blocking the vent
holes. Very common problem found during our NRG Audit inspections.
This is what is recommended on the
outside of the home if you do not have a
soffit. If you have a soffit, add 8"x12" screened vents every eight feet of soffit.
This procedure gives your attic the air it needs to vent
properly. In cold climates this equates to adequate moisture removal and
the elimination of the associated problems like mold growth and wood rot.
In hot climates, the super heated attic air can flow out the upper vent (if you
have them), and draw cooler air in around the house. This what your
architect and builder expected. However, in most homes the insulation
contractor may have plugged up some or all of your soffit
vents. Our home energy auditors have found most homes have this problem. If you have
questions about your existing attic vents, take a few digital pictures and send
them to us for evaluation. This will be a free service as we fine tune our
online NRG Audit coming soon. Take advantage of our knowledge and free
advice! Please, no more than five pictures. Take one of each side of
the home noting to make photos of the soffits vents (if any), gable vents (if
any), and one or two shots of the attic.
Step by Step Soffit Venting

The soffits on this home were
completely blocked making the attic like an oven increasing energy costs and
making the upstairs unbearable during the summer.
This is very common in
homes of all ages, even brand new homes across the
country.

Cutting holes in
the plywood soffit to allow intake air to cool the attic.

Once we get the holes cut, simply cover them with 8"x12" louvered
grills. They are available in white, silver or dark
brown.

The
completed installation. Efficient, inexpensive and lasts
forever. Paint the grills after the installation to match the
soffits and they blend right in.
Homes we
have upgraded attic vents on have significantly reduced attic temperatures
during the summer. This means lower A/C bills, more comfort and A/C
equipment lasts longer.
A 20" x 24" dormer
pictured here and a 16" round gable vent. The yellow scale pictured above is
three feet long for reference. These are the vents of choice
for the best movement of air out of your attic.
This vent can be applied to 3/12 and 4/12 pitch
roofs. 5/12 now available.
Dormer vents installed correctly on the back side of an
apartment building. The lower vents on the roof are intake vents, the
upper vents are exhaust vents. This type of venting, if correctly sized to
the attic size and volume, can adequately vent the hot air out during the summer
and moisture during the winter.
These are not seen from the front of
the building and therefore do not detract from the
aesthetics.
POWER
VENTING
This shows a typical home store attic fan installed on a gable vent inside
the attic. Although the mounting looks secure, the application is
incorrect since the space around the fan is not blocked off. The fan will
create a negative pressure behind the fan and will draw air from the closest
point, in this case, from vent openings around the fan.
This means very little air will
be exhausted from the attic and most of it will be drawn in around the fan.
The open area around the fan shroud (the round ring), needs to be
blocked off with cardboard or wood to make this type of installation
effective.
Power Fans:
Natural attic venting is best but in many homes a powered attic
ventilator is more cost effective, especially in tile roofs.
STAY AWAY FROM UNDER POWERED SOLAR
ATTIC FANS, THEY JUST DON'T MOVE ENOUGH VOLUME. Great idea, not enough
power.
We now import a
vibration free, powerful, reliable powered attic fan manufactured in Germany.
This attic fan is unlike any other available.
We include an
adjustable thermostat and an optional mounting box with this system. This
fan features an external rotor to which the fan blades are welded.
This unique design reduces blade flex and vibration and eliminates one of the
shaft bearings.
The bearings are sealed and never need
attention. Install it, set the thermostat and forget about it.
14" 1800 CFM fan shown
here
In homes that have gas appliances such as
water heaters or furnaces in the attic, great care must be taken to insure
adequate intake venting (gables/soffits), is provided so as to not create a
negative pressure that will draw combustion gasses down the chimney of gas
appliances. Installing an attic fan in this application has the
potential for fire or filling your attic with carbon dioxide. Just make
certain there is sufficient intake openings to circumvent this potential
hazard.
Construction
Features
- Motor: 1/4 Hp
115/1/60 (compare this home store fans rated at 1/8hp)
- Adjustable thermostat included
- Costs 2
cents per hour at 10 cents per KWH
- CFM @ 0.0 " SP: 1839
cubic feet per minute (Actual, not estimated)
- Integral Blades and
External Rotor allowing precision balancing
- Formed steel wall
panel with Venturi
- Shallow profile with
no protruding motor
- External rotor
motor, class B insulation.
- Quality design provides
long and maintenance free operation for many years
-
No maintenance required
- Automatic Reset
Thermal Overload Protection
- Electro statically
applied polyester/epoxy urethane powder coat finish
- Self lubricating,
sealed for life precision ball bearings
- Can be installed in gable
vent or under dormer vent
Specifications
Performance Data
Fan Model |
RPM |
Volts |
Max. Watts |
Max. Amps
|
0" |
.100" |
.125" |
.25" |
.375" |
.5" |
Sones** |
| 8"
PAV |
1550 |
115 |
45 |
0.41 |
304 |
246 |
224 |
74 |
- |
- |
4.1" |
10" PAV
|
1500 |
115 |
68 |
0.62 |
624 |
558 |
533 |
377 |
132 |
- |
7.9 |
| 12"
PAV |
1400 |
115 |
130 |
1.19 |
1208 |
1069 |
1030 |
797 |
- |
- |
9.4 |
| 14" PAV |
1200 |
115 |
245 |
2.24 |
1839 |
1654 |
1599 |
1295 |
- |
- |
9.6 |
| 16"
PAV |
1400 |
115 |
458 |
4.19 |
3054 |
2882 |
2839 |
2570 |
2198 |
1699 |
12.0 |
| 18" PAV |
1550 |
115 |
698 |
6.39 |
4115 |
3895 |
3840 |
3549 |
3239 |
2908 |
14.3 |
20"
PAV
|
1100 |
115 |
435 |
3.98 |
3693 |
3368 |
3279 |
2775 |
1429 |
- |
10.7 |
20" PAV
|
1450 |
115* |
916 |
8.39 |
4949 |
4682 |
4615 |
4274 |
3917 |
3445 |
16.4 |
22"
PAV
|
1000 |
115* |
756 |
6.92 |
5629 |
5248 |
5153 |
4432 |
- |
- |
12. |
| 25" PAV |
1000 |
115* |
1134 |
10.38 |
7858 |
7355 |
7230 |
6567 |
- |
- |
14.8 |
** The sound ratings shown are loudness
values in fan sones at 5ft. (1.5m) in hemispherical free
field
calculated per AMCA Standard 301. Values shown are for installation Type A: Free
inlet fan
sone levels. All sone values shown are calculated at 0.1"
(static pressure in inches W.G.).

Which fan looks like it's more
efficient at moving air out of your attic? Over the years we have found
home store attic fans to be a liability to our installations and the only weak
link in our proven NRG Package. Since a properly installed radiant
barrier increases attic air temperature by keeping
unwanted heat from getting to the insulation, removing this wasted heat has
forced us to become experts in attic ventilation.
Home store fans like the
one pictured are under powered, last one year (if that), and the Chinese
thermostat is inaccurate, sticks on (or off), creates call backs and
problems. Sure the nice one costs more but like anything else, you get
what you pay for.

14" fan shown with
optional fan mounting box (see below)
We fabricate this sheet metal fan
box for our Phoenix installations and thought we should offer it to our
VI customers as well.
The design allows for a smoother discharge of
air as it fully takes advantage of the aerodynamic design of
the shroud and large side flanges makes it much easier to
install. Cuts the installation time in half.
This is how the fan will look. The fan is
mounted to the sheet metal box and there is 15' piece of 14 gauge Romex already
pre-wired to the fan and thermostat. We even provide
a 2"x4" mounting box to mount the thermostat so all we need to do is run
a 115v power supply to the thermostat, mount the fan shroud to the wall, set the
thermostat to 105f and call it a day.
TCM Window
Film
Attic
Insulation Wall
Insulation Attic
Fans Installations
FAQ Background Tubular Skylights LEED
Programs Independent
Research
WAPA
St. Croix Environmental
Association VI Energy Office
HOME Email Us
340 772 3039
